General Information
Model Type KING CS SERIES
Model Name KIN-625CS

AC Input
AC Input Capacity on Battery 625VA
AC Input Voltage 120V +/- 25%
AC Input Frequency 50 or 60 Hz +/-10% (auto sensing)

AC Output
AC Output Voltage Sine wave at 120V +/-10%
AC Output Frequency 50 or 60 Hz +/- 1%
AC Output Voltage Regulation AVR automatically increase output voltage 15% while nominal -9% to -25% utility voltage be connected; AVR automatically decrease output voltage 13% while nominal +9% to +25% utility voltage be connected
AC Output Transfer 2/4 milliseconds, including detection time

Protection
Protection Spike 480 Joules, 2ms
Protection Overload UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec
Protection Unit Circuit breaker for overload & short circuit protection
Protection 10 BaseT Network (UTP, RJ-45) compatible jacks
Protection Short Protection UPS output cut off immediately or input circuit breaker protection

Battery
Battery Type Sealed, maintenance-free lead acid batteries with 3-6 years typical lifetime
Battery Typical 6 hours (to 90% of full capacity)
Battery Protection Auto discharge protection
Battery Run Time 25 - 35 minutes

Physical
Physical Weight kgs Tower 6.5
Physical Weight lbs Tower 14.3
Physical Shipping Weight kgs 7.0
Physical Shipping Weight lbs 15.4
Physical Dimension mm Tower 97x320x135
Physical Dimension inch Tower 3.8x12.5x5.3

Alarm
Alarm Battery Backup Slow beeping sound (about 0.47 Hz)
Alarm Battery Low Rapid beeping sound (about 1.82 Hz)
Alarm Overload Continuously beeping sound

Interface
Interface RS-232 Detect battery low; Schedule UPS on/off; Display AC input/output power status

Environment
Environment Ambient 3500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg C
Environment Audible <40dBA (1 meter from surface)